National Stock Number(NSN): 5925-00-755-8187 (5925007558187, 007558187)
| NIIN: |
00-755-8187⛔ |
Item Name: |
CIRCUIT BREAKER |
INC: |
00136
|
| FSC: |
5925
|
Assignment Date: |
|
CRIT: |
|
IIG: |
00136 |
| ISC: |
3 |
Date Standardized: |
|
HMIC: |
|
DODIC: |
|
| NSC: |
8 |
Cancellation Date: |
Jun-04-1997 |
PMIC: |
|
FIIG: |
A030A0 |
| ESD: |
|
Schedule B: |
|
DEMIL: |
B |
DEMIL INT: |
|
| TIIC: |
4 |
Originator: |
|
ADPEC: |
|
RPDMRC: |
|
| Part Number |
CAGE |
Company |
Status |
RN CC |
RN VC |
DAC |
RN AAC |
RN FC |
RN SC |
RN JC |
SADC |
HCC |
MSDS |
|
D7271-1-30 |
82647
|
SENSATA TECHNOLOGIES, INC. |
H |
3 |
2 |
|
|
|
|
|
|
|
|
Technical Characteristics Information
| MRC |
Requirement Statement |
Reply Statement |
| ADTV |
CASE MATERIAL |
PLASTIC |
| AKPX |
POLE QUANTITY |
1 |
| AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
THD BUSHING |
| CMLP |
THREAD QUANTITY PER INCH |
32 |
| CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
30.0 AMPERES AC AND 5.0 AMPERES DC |
| CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
120.0 AC AND 30.0 DC |
| CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
3500.0 AC AND 4000.0 DC |
| CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT |
| CPRJ |
TRIP RELEASE METHOD |
THERMAL |
| CPRL |
TRIP RELEASE CHARACTERISTIC |
TIME DELAY |
| CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
138.0 |
| CPRP |
ULTIMATE TRIP TIME PER POLE IN SECONDS |
3600.000 NOMINAL |
| CPRQ |
RESET METHOD |
MANUAL |
| CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
| CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
1 PUSH-PULL |
| CPRW |
ACTUATOR FUNCTION |
RESET |
| CQJX |
NOMINAL THREAD SIZE |
0.468 INCHES |
| CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
25.000 MINIMUM AT 200 PCT AND 100.000 MAXIMUM AT 200 PCT AND 10.000 MINIMUM AT 400 PCT AND 25.000 MAXIMUM AT 400 PCT |
| CQXF |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED |
EXPLOSION RESISTANT |
| TTQY |
TERMINAL TYPE AND QUANTITY |
2 SCREW |
Replacement & Obsolete Information
| Replaced / Replacement NIIN Information |
|